Chapter 6 Fault Code Information_VFD-B Series 
6-4   
Revision 10/2005, BE13, SW V4.08 
Fault Name  Fault Descriptions  Corrective Actions 
 
External Fault 
1.  Input EF (N.O.) on external terminal is closed to GND. 
Output U, V, W will be turned off. 
2.  Give RESET command after fault has been cleared. 
 
Emergency stop 
1.  When the multi-function input terminals MI1 to MI6 are 
set to emergency stop (setting 19 or 20), the AC motor 
drive stops output U, V, W and the motor coasts to stop. 
2.  Press RESET after fault has been cleared. 
 
Internal EEPROM can not be 
programmed. 
Return to the factory. 
 
Internal EEPROM can not be 
read. 
Return to the factory. 
 
U-phase error 
 
V-phase error 
 
W-phase error 
 
OV or LV 
 
Current sensor error 
 
OH error 
Return to the factory. 
 
Software protection failure 
Return to the factory. 
 
Password is locked. 
Keypad will be locked. Turn the power ON after power OFF 
to re-enter the correct password. See Pr.00-07 and 00-08. 
 
Auto accel/decel failure 
1.  Check if the motor is suitable for operation by AC motor 
drive. 
2.  Check if the regenerative energy is too large. 
3.  Load may have changed suddenly.