Appendix C  How to Select the Right AC Motor Drive_VFD-B Series 
Revision 10/2005, BE13, SW V4.08     C-3 
2.3 When it is running continuously 
The requirement of load capacity should be less than the capacity of AC motor drive(kVA) 
The requirement of load capacity= 
d
u
u
MK
cos
MPk
 the capacity of AC motor drive (kVA) 
The motor capacity should be less than the capacity of AC motor drive 
duuuu
3
103 MM IVk  the capacity of AC motor drive (kVA) 
The current should be less than the rated current of AC motor drive(A) 
du MIk  the rated current of AC motor drive(A) 
Symbol explanation 
M
 
: Motor shaft output for load (kW) 
ӯ 
: Motor efficiency (normally, approx. 0.85) 
cos  
: Motor power factor (normally, approx. 0.75) 
MV  
: Motor rated voltage(V) 
M
 
: Motor rated current(A), for commercial power 
k  
: Correction factor calculated from current distortion factor (1.05 - 1.1, depending on PWM 
method) 
1CP  
: Continuous motor capacity (kVA) 
Sk  
: Starting current/rated current of motor 
Tn  
: Number of motors in parallel 
Sn  
: Number of simultaneously started motors 
2
GD  
: Total inertia (GD
2
) calculated back to motor shaft (kg m
2
) 
L
 
: Load torque 
At  
: Motor acceleration time 
N  : Motor speed