Chapter 2 Installation and Wiring_VFD-B Series 
2-24   
Revision 10/2005, BE13, SW V4.08 
Terminal Symbol  Terminal Function 
Factory Settings (SINK) 
ON: Connect to DCM 
ACI 
Analog current Input 
ACM
ACI
Internal Circuit
CI circuit
 
Impedance:  250ȍ 
Resolution:  10 bits 
Range:  4 ~ 20mA = 
  0 ~ Max. Output 
Frequency (Pr.01-
00)  
Selection:  Pr.02-00, Pr.02-13, 
Pr.10-00 
Set-up:  Pr.04-11 ~ Pr.04-14 
AUI 
Auxiliary analog voltage input 
ACM
AUI
+10~-10V
Internal Circuit
AUI circuit
 
Impedance:  47kȍ 
Resolution:  10 bits 
Range:  -10 ~ +10VDC = 
  0 ~ Max. Output 
Frequency (Pr.01-
00)  
Selection:  Pr.02-00, Pr.02-13, 
Pr.10-00 
Set-up:  Pr.04-15 ~ Pr.04-18 
AFM 
Analog output meter 
Internal Circuit
ACM circuit
FM
CM
0~10V
Max. 2mA
ondometer
 
0 to 10V, 2mA 
Impedance:  470ȍ 
Output current  2mA max 
Resolution:  8 bits 
Range:  0 ~ 10VDC 
Function:  Pr.03-05 
ACM  Analog control signal (common)  Common for AVI, ACI, AUI, AFM 
Control signal wiring size: 18 AWG (0.75 mm
2
) with shielded wire.