Chapter 13 Warning CodesC2000 Plus 
 
ID No.  Display on LCD Keypad  Warning Name  Description 
24 
 
Over slip warning 
(oSL) 
Over slip warning. 
By using the maximum slip (Pr.10-
29) as the base, when 
the drive outputs at constant speed, and the F>H or F<H 
exceeds Pr.07-29 level and Pr.07-30 set
Pr.07-29 = Pr.10-29.   
Action and Reset 
Action condition 
When the drive outputs at constant speed, and F>H or F<H exceeds the Pr.07-
29 level 
Action time  Pr.07-30 
Warning setting parameter 
Pr.07-31=0 Warning 
0: Warn and keep operation 
1: Fault and ramp to stop 
2: Fault and coast to stop 
3: No warning 
Reset method 
When Pr.07-31=0 and 
when the drive outputs at constant speed, and F>H or F<H 
no longer exceeds the Pr.07-29 level, the oSL warning automatically clears. 
Reset condition  N/A 
Record  N/A 
Cause  Corrective Actions 
Check if the motor parameter is 
correct 
Check the motor parameter. 
The load is too large  Decrease the loading. 
Check if the settings for Pr.07-29, 
Pr.07-30 and Pr.10-29 are 
set 
Check the parameter settings for oSL protection.