65
curves and their parameters are examined in Main Menu> Protection Settings> Protection and
Reset Curves.
4.3.2.4.7 Reset Delay
According to the menu settings, exceeding 5.00 In and without breaker tripping, It was
selected to count the DMT (constant time) reset time (0.04 s) after the current has dropped
below 5.00 In. Thus, after the current falls below the threshold, 40 ms will be counted. If the
threshold is not exceeded until the end of this period, the protection function trip time counter
will be reseted. Reset delay thresholds are in the range of (0-60).
4.3.2.4.8 RTMS

is activated when selected as IDMT. The setting range of the factor can be selected within the
range (0,025 - 5).
4.3.2.4.9 Trip Zone

4.3.2.4.10 Torque Angle
The torque angle must be entered as the zone where the relay is most sensitive to fault
currents. You may notice differences in varied systems. 
Torque point is obtained by adding the entered torque angle to the angle of the phase-to-phase
voltage. Protection is carried out in the area of the Torque zone, as much as the Torque Area.
4.3.2.4.11 Direction Mode
