The number of cycles used to calculate the rate at which frequency change rate protection is
used.
4.3.6.2.3 Number of Valid
It is the number of controls used to calculate speed in frequency change rate protection.
4.3.6.2.4 Inhibit>20 Hz/s
It is the setting used to prevent protection when the speed is above 20 Hz / s in frequency
change rate protection. If it is active, it will block; if it is passive, there will be no
intervention. This can prevent the protection from being triggered in the wrong
measurements.