Power Protection Settings Display
Directional Active-Reactive Over and Low Power Protection Vectors
4.3.5.1 32OP Directional Active Over Power
The Directional Active Over Power settings are Main Menu> Protection Settings> Power
Protection Settings> Directional Active Over-Power Protection
This protection starts when the total active power reading of the device exceeds the starting
value.
This protection starts when the total active power reading of the device exceeds the starting
value. The unit of starting value is In x W. This protection only works according to the DMT