65
Modbus Offset Register
Description
* System=sum of three phases
44046 4045 kVAh L3 MSW “
44047 4046 kVA L1 Individual Phase Apparent Powers (kVA)
44048 4047 kVA L2 “
44049 4048 kVA L3 “
44050 4049 Displacement PF L1 Individual Phase displacement Power Factor (PF)
44051 4050 Displacement PF L2 “
44052 4051 Displacement PF L3 “
44053 4052 Apparent PF L1 Individual Phase apparent Power Factors (PF)
44054 4053 Apparent PF L2 “
44055 4054 Apparent PF L3 “
44056 4055 Amps L1 Individual Phase Currents (A)
44057 4056 Amps L2 “
44058 4057 Amps L3 “
44059 4058 Volts L1 to Neutral Individual Phase to Neutral Voltages (V)
44060 4059 Volts L2 to Neutral “
44061 4060 Volts L3 to Neutral “
44062 4061 Time Since Reset LSW Seconds since KWH register was reset. LSW
44063 4062 Time Since Reset MSW Seconds since KWH register was reset. MSW
44064 4063 Data Tick Counter
Internal sample count (gets cleared every minute):
may be used to determine if sample read is a newer
sample than last read.
44080 4079 kW System Average
Equals KWH_SYSTEM_L&M ÷ (TimeSinceReset_L&M
seconds /3600 seconds/Hr) (resettable)
44081 4080 kW Demand System Min System Minimum Demand (kW)
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com