EasyManua.ls Logo

Det-Tronics LS2000 - Important Safety Notes; Caution (Wiring Procedures); Caution (Hazardous Area Use); Caution (User Serviceability)

Det-Tronics LS2000
45 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2.2 95-871412
TEMPERATURE RANGE—
Operating: 55°C to +75°C (–67°F to +167°F)
Relay version: 55°C to +6C (67°F to +149°F)
Storage: 55°C to +85°C (–67°F to +185°F)
Hazardous Locations: Refer to
the
appropriate Approval/
Certification
Appendix
for correct ambient
temperature range.
HUMIDITY—
5 to 99% relative humidity; designed for outdoor
applications.
OPERATING PRESSURE—
91.5 - 105.5 kPA non-compensated.
MEASUREMENT RANGE—
0-5 LFL-meters.
Note: A Negative Zero Drift fault is indicated at
9% of full scale.
INTERFERENCE RESISTANCE—
Immune to sun and flare radiation, tested to
800 ±50 W/m
2
at ≥ 3° to optical axis and
common contaminants.
SELF-DIAGNOSTIC TEST—
Fail-Safe operation ensured by performing all
critical tests once per second.
MODULE HOUSING MATERIAL—
316 stainless steel (CF8M).
CONDUIT ENTRY OPTIONS—
3/4 inch NPT or M25, with two entries for
transmitter and four entries for receiver.
OPTICS PROTECTION—
Microprocessor controlled heated optics
mitigate against ice and dew formation. Brow
provides a degree of protection against
windblown dirt and rain. See “Mounting
Instructions” for brow installation procedure.
INGRESS PROTECTION—
NEMA Type 4X certified,
IP66/67 (Det-Tronics verified).
WIRING—
Field wiring screw terminals are UL/CSA rated
for up to 14 AWG shielded wire, and are DIN/
VDE rated for 2.5 mm
2
wire. Screw terminal
required torque range is 3.54.4 lb.-in. (0.4-0.5
Nm).
The receiver can be wired using 3 or 4 wires.
The transmitter requires two wires (power only).
The use of shielded wiring is recommended.
Field wiring for supply connection must be rated
to 95°C (203°F).
CERTIFICATION—
For complete approval details, refer to the
appropriate Appendix:
Appendix A - FM
Appendix B - CSA
Appendix C - SIL
DIMENSIONS—
See Figure 4 for dimensions of the transmitter
and Figure 5 for dimensions of the receiver.
MOUNTING & ALIGNMENT BRACKET
ADJUSTMENT RANGE—
±12 degrees from center, both vertical and
horizontal.
WARRANTY—
5 year limited warranty.
10 year warranty on IR source.
SHIPPING WEIGHT—
Transmitter and receiver with mounting hardware:
85 pounds (38 kg)
Replacement Transmitter: 23 lbs (10.4 kg)
Replacement Receiver: 20 lbs (9 kg)
Transmitter Electronics Module: 10.4 lbs (4.7 kg)
Receiver Electronics Module: 7.8 lbs (3.6 kg)
FM
APPROVED
®

Related product manuals