Model FP-700
FP-700 Instruction Manual Rev. 5.1 Page 36 of 46
Check validity of span gas and flow rate (check MFG date on cal cylinder).
If using Splashguard with Integral Cal Port, must use Calibration Wind Guard or air movement can
compromise span gas delivery.
Make sure correct Cal Factor is set
Check for obstructions through stainless steel sinter element (including being wet).
Replace the plug-in sensor.
Clearing Fault
Probable Causes: Failed Sensor, Cal Gas not removed at appropriate time, problems w/ cal gas and delivery, or
Background combustible gases preventing clearing.
Confirm that no combustible gasses are present in background.
Check Bridge Voltage (should be 2.7 +/- 0.2VDC).
Check validity of span gas and flow rate (check MFG date on cal cylinder).
Make sure correct Cal Factor and Gas Factor is set
Check for obstructions through stainless steel sinter element (including being wet).
Replace the plug-in sensor.
Poor Calibration Repeatability
Probable Causes: Failed Sensor, use of wrong Cal Gas, problems w/ cal gas and delivery, or Poison or Inhibitor
Gases.
Check for adequate Sensor Life.
Check Bridge Voltage (should be 2.7 +/- 0.2VDC).
Check validity of span gas and flow rate (check MFG date on cal cylinder).
Check for obstructions through stainless steel sinter element (including being wet).
Evaluate area for presence of poisoning or inhibiting gases as listed in Section 2.3.
Increase calibration frequency.
Note the sensor’s serial # and report repetitive problems to Detcon’s Repair Department.
Replace plug-in sensor.
Unstable Output/ Sudden spiking
Possible Causes: Unstable power supply, inadequate grounding, or inadequate RFI protection.
Verify Power source is stable.
Verify field wiring is properly shielded and grounded.
Contact Detcon to optimize shielding and grounding.
Nuisance Alarms
Check condulet for accumulated water and abnormal corrosion on terminal blocks.
If nuisance alarms are happening at night, suspect condensation in condulet.
Add or replace Detcon’s Condensation Prevention Packet P/N 960-202200-000.
Investigate the presence of any other combustible gases that may be causing sensor response.
Processor and/or Memory Faults
Recycle power in attempt to clear problem
Restore Factory Defaults This will clear the processor’s memory and may correct problem.
Remember to re-enter all customer settings for range and cal gas level after Restore Factory Defaults.