Service and Maintenance
6
25 895 0 24 232 3 25 896 0
6.7 Accessories
6.7.1 Battery
Keep battery clean and dry.
Undo dirty clamps.
Clean terminal posts (+ and -) and clamps of the
battery, and grease with acid-free and acid-
resistant grease.
When reassembling, ensure that clamps make
good contact. Do up clamp bolts finger tight.
Remove caps 1.
If testers 2 are used, the electrolyte should come
up to their base.
If testers are not used, the electrolyte level should
be 10-15 mm above the top of the plates.
If necessary, top up with distilled water.
Replace caps.
Measure the electrolyte density of individual
cells with a commercial hydrometer.
The hydrometer reading (see table on following
page) indicates the state of charge.
During measurement, the temperature of the
electrolyte should preferably be 20 °C.
6.7.1.3 Checking Electrolyte
Density
6.7.1.2 Checking Electrolyte Level6.7.1.1 Checking Battery and Cable
Connectors