ElectroVap MC
Electrical features
P ALERTS TROUBLE CAUSES / ACTIONS OPTION
P0 ALERT
A power phase is missing
Check power supply, fuses
or power circuit breaker
(general power switchboard)
Power phase
detection device is
required
P1 ALERT
Unit on steam demand
and contactor still on
F1 fuse (2A) or contactor
coil failure.
CHANGE FUSE OR
CONTACTOR
Standard
P2 ALERT
Idle demand and
contactor still off
CHANGE CONTACTOR Standard
P3 ALERT
Inlet valve constantly
open
Check correct water inlet
pressure (1 to 6 bar).
CHANGE INLET VALVE
Standard
P4 ALERT
Cylinder is not filling
correctly
Water supply failure or low
water pressure. Drain valve
failure.
CHANGE INLET VALVE –
CLEAN DRAIN VALVE
Standard
P5 ALERT
Cylinder not draining
correctly
Blockage at the drain valve.
Drain valve coil failure.
CLEAN or CHANGE DRAIN
VALVE – REPLACE COIL-
CHANGE or CLEAN
CYLINDER
Standard
P6 ALERT
Water leakage in cylinder
part
Cylinder leaking at the
gasket.
CHANGE GASKET or
CYLINDER
Water leakage
detection device is
required