Communication solutions for power utilities
UNIVERSAL TELEPROTECTION TPU-1
INSTALLATION AND COMMISSIONING MANUAL Web version TPU-1R - Rev. 5.9 (May 2018)
f) Final checks.
- In the situation where the equipment is blocked, then it should be unblocked.
- If any of the line interface modules is in permanent local loop, then it should be
deactivated.
- Check that any terminal of the terminal block is disconnected.
- Set the terminal clock by date and time using the Clocks and synchronism option
of the Equipment menu.
- Set the periodicity of the automatic test of the link by means of the Loops, Blocking
and Test option of the Alignment menu.
- Reset the chronological register using the Chronological register option of the
Monitoring menu.
- Reset the transmitted and received command counters using the Counter reset
option of the Alignment menu.