IC100C Series PRELIMINARY
1592015000 Manual IC100C Series 28/05/03 Page 15 di 38
A07 Anti freeze alarm Digital input active
anti freeze probe
Pbr < AR03 for
minimum AR05
seconds
Open collector / alarm relay ON
Buzzer ON
General alarm icon lighted
Alarm code on display
Automatic.
It turns to manual after Ar06
events in 1 hour.
Manual:
the event expires if Pbr >
(AR03+AR04), then proceed
with manual reset.
A07 Anti freeze alarm
motocondensing
unit
Digital input active
CF01=6,7 and
CF05=2
Open collector / alarm relay ON
Buzzer ON
General alarm icon lighted
Alarm code on display
Automatic.
It turns to manual Ar06 events
in 1 hour.
Manual:
the event expires, then proceed
with manual reset.
A08 Water flow alarm
(air/water
water/water;
Supply air fan
thermal protection
(air/air)
Digital input active
for AL06 duration.
Open collector / alarm relay ON
Buzzer ON
Flow alarm icon lighted
Alarm code on display
Automatic.
It turns to manual after Ar05
events in 1 hour.
Manual:
the event expires for AL07,
then proceed with manual
reset.
A09 Compressor 1
thermal protection
alarm
Digital input active Open collector / alarm relay ON
Buzzer ON
General alarm icon lighted
Alarm code on display
Manual:
the event expires, then proceed
with manual reset.
After AL09 events in 1 hour
and digital input not active, set
AL10=0 to resume.
A10 Compressor 2
thermal protection
alarm
Digital input active Open collector / alarm relay ON
Buzzer ON
General alarm icon lighted
Alarm code on display
Manual:
the event expires, then proceed
with manual reset. After AL09
events in 1 hour and digital
input not active, set AL10=0 to
resume.
A11 Condenser fan
thermal protection
alarm
Digital input active Open collector / alarm relay ON
Buzzer ON
General alarm icon lighted
Alarm code on display
Manual:
the event expires, then proceed
with manual reset.
A12 Defrost error alarm End defrost after
dF07 (Max defrost
length) with
dF02=2
Only alarm code on display Automatic:
with next proper defrost cycle.
Proceed with manual reset.
A13 Compressor 1
maintenance
warning
Running hour >
CO14
Open collector / alarm relay ON
Buzzer ON
Maintenance icon lighted
Alarm code on display
Manual:
Proceed with the hour reset
procedure 16.6
A14 Compressor 2
maintenance
warning
Running hour >
CO15
Open collector / alarm relay ON
Buzzer ON
Maintenance icon lighted
Alarm code on display
Manual:
Proceed with the hour reset
procedure 16.6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the dixell ichill IC100C series and is the answer not in the manual?

dixell ichill IC100C series Specifications

General IconGeneral
Branddixell
Modelichill IC100C series
CategoryController
LanguageEnglish

Related product manuals