8860 Installation and Programming Guide | Digital Monitoring Products 21
REFERENCE
Keypad Bus Wiring Specifications
DMP recommends using 18or 22-gauge unshielded wire for all keypad and AX-Bus/LX-Bus circuits. Do not use
twisted pair or shielded wire for AX-Bus/LX-Bus and Keypad Bus data circuits. All 22-gauge wire be connected to
a power-limited circuit and jacket wrapped.
When powering an 8860 from the keypad bus, to maintain auxiliary power integrity when using 22-gauge wire
do not exceed 100ft. When using 18-gauge wire do not exceed 500ft. To increase the wire length or to add
devices, install an additional power supply that is listed for Fire Protective Signaling, power limited, and regulated
(12/24VDC nominal) with battery backup.
Maximum distance for any one bus circuit (length of wire) is 2,500ft regardless of the wire gauge. This distance
can be in the form of one long wire run or multiple branches with all wiring totaling no more than 2,500ft. As wire
distance from the panel increases, DC voltage on the wire decreases. Maximum number of AX-Bus/LX-Bus devices
per 2,500ft circuit is 40.
Maximum voltage drop between the panel (or auxiliary power supply) and any device is 2VDC. If the voltage at
any device is less than the required level, add an auxiliary power supply at the end of the circuit. When voltage is
too low, the devices cannot operate properly.
For additional information refer to the panel’s Installation Guide.
Compatibility
XT Series Panels with Version 221 or higher and Level G Hardware or higher
XR Series Panels with Version 221 or higher
V-4000, V-5000, and V-6000 Series Cameras
Ordering Information
8860-B 8860 7-Inch Touchscreen Keypad (Black)
8860-W 8860 7-Inch Touchscreen Keypad (White)
300-8860-4 Replacement 4-Wire Harness (Keypad Bus Connection)
300-8860-PWR-B Replacement Power Harness (Wi-Fi Connection, Black)
300-8860-PWR-W Replacement Power Harness (Wi-Fi Connection, White)
SPECIFICATIONS
Operating Voltage 12 VDC
Current Draw 300 mA at 12 VDC
Current Load in Alarm 350 mA at 12 VDC
Dimensions 7.67” W x 4.57” H x 0.55” D
Display Size 7” (1024 x 600)
Note: Each panel allows a specific number of supervised keypads.