56
ED50/ED100/ED250 09-2021DL4617-003
dormakaba ED50/ED100/ED250 OHC Header
Setup and Troubleshooting Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting
Description
Suppression of safety sensor on swing
(hinge) side during initialization drive

 - 
Safety sensor on swing side is active during an initialization drive after a power on
reset.
With SP set to , operator will disregard swing side safety sensor during
initialization drive.
After a power on reset, operator starts an initialization drive at slow speed.
The initialization drive cannot be completed if safety sensor on hinge side is, or
has been triggered.
Delayed opening time for locking mechanism
Delayed opening time delay starts as soon as door opening pulse has been
generated.
Door opens on expiration of time delay.
If parameter is set to "" and input for locking feedback contact is closed, door will
not perform a preload Pu before door unlocks.
Since various motor locks do not have feedback contacts, a delay of up to  seconds
is possible

 - 
* 
ms
*
Door preload prior to unlocking
Door preload prior to unlocking; force with which door is pushed in the "closed"
direction before door is opened.
The door may need to be pushed in closing direction (preload) in order to release
electric strike to insure door opens.
Preload time is set by parameter Ud, delayed opening time for locking mechanism.
To maintain long service life, set preload force only as high as necessary.

 - 
Power reserve module SVP-PR  test

 - 
Test off
. SVP-PR  power reserve module test is performed once every  hours, or
 minutes after AC power has been turned on. In event of an error:
Unlocking is not performed and no automatic door movements are initiated.
Error code E  is displayed, See Appendix B, troubleshooting error codes.
. SVP-PR  power reserve module can be used but must be tested on a regular
basis if using:
SVP- DCW emergency escape motor lock with automatic latching action.
M-SVP  DCW emergency escape lock.
. Test is automatically activated if a fire protection module is recognized in
conjunction with SVP- DCW or M-SVP  DCW locks.
TS
Static force in opening direction
ED: Low energy only.
ED/ED: can be configured for full energy using Parameter F.
Static force in opening direction (basic parameter for wind load control).
Static force on door closing edge can be changed using this parameter.
After parameter adjustment, internal monitoring system checks if parameter setting
is admissible. If setting exceeds admissible value, the setting is alternately displayed
with the permissible value.
. After parameter set, verify setting meets ANSI/BHMA standards. See Chapter .

Low Energy
ANSI/BHMA A.
Parameter
setting *
 N -  N
. lb f - . lb f
6
Full Energy
ANSI/BHMA A.
Parameter
setting *
 N -  N
. lb f - . lb f
6
A.. Driving parameters detail.