Specifications
0.02 to 0.03 and 0.02 to 0.03 (water alarm),
0.23 to 0.25 and 0.23 to 0.25 (hydrocarbon alarm)
Multi-Drop Restriction
Maximum points per channel = 12 points,
924B and DMP Probes = 4 points,
ISIM Smart Sensors = 1 point
Devices can be mixed in any combination to hold a max-
imum of 12 points on one channel
Connections: Red = Power, Black = Signal, Shield = Ground
NOTE: *This is the maximum length of wire to be used to connect all sensors on one channel.
This length includes the wire from the Barrier to each sensor board in the string.
30-0236-LW Dimensions
Installation
WARNING: Make sure you read and fully understand the warnings and
information found in the Hazardous Areas section of your console's
Installation Guide before you install or do the servicing of this sensor.
CAUTION: ALWAYS obey Local and National Electrical Codes applicable to
the installation location.
Make sure that the cables (gas and oil resistant OPW Fuel Management
Systems part # 12-1030) from the field wiring to the controller are in conduit
that is dedicated to intrinsically safe wiring.
Use wire-nuts and epoxy-resin seal-packs for field connections (refer to M00-
390008 Waterproof Electrical Connections for information).
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 104