7.3 Electrical Connection
To make a connection to 110-220 VAC:
l De-energize all power switches at the main electrical panel.
l Make sure to use the applicable connections to connect the console to the electrical panel.
l A Power Supply Cord is not supplied: Use an applicable, approved ELBZ/7 type power cord.
l Make sure the power plug is connected to the ground and protected against short circuits and
power surges.
l Make sure to connect the I.S. ground to the site's earth system. Use a dedicated 4.0 mm
2
copper
cable (see the illustration below).
.
l The power cord must be easy to identify and must have easy access so it can be used to remove
power.
WARNING: There is high voltage within the console.
IMPORTANT: The electrical connection procedure must be done by approved personnel
only!
7.4 Installation Procedure
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 18