11.3 Spacer Assembly (6-3/4 RA SS) and Adjustment
IMPORTANT: The minimum inner diameter for a riser is 52 mm (2.05 in.). This gives an
allowance for the head gaskets so the probe can move freely inside the riser
The DMP Probe can be installed in a minimum 52 mm (2.05 in.) inner diameter riser without modification. If
the probe is to be installed in a riser with an inner diameter up to 4-inches (101.6 mm), a spacer must be
installed. This will keep the probe in the center of the riser and in a vertical position through the bottom of the
tank.
The Probe Spacer kit contains:
l One (1) stainless steel, flexible spacer.
l Two (2) M3x8 screws
l Two (2) M3 nuts
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 46