EasyManua.ls Logo

Dover ProGauge MagLink LX Plus - 14.8 Dual Float Brine Sensors

Dover ProGauge MagLink LX Plus
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14.8 Dual Float Brine Sensors
Smart Sensor Equipped with Intellisense™ Technology
30-0232-D-10B (for Containment Sump) and 30-0232-D-20B (for Fiberglass Tanks)
Description
IMPORTANT: This float body is the same as the 30-0232-D-10 / D-20 and 30-0232-DH-10 /
DH-20 (DH-XX has a carbon-polymer strip in the bottom). Look at the label to make sure you
have the correct sensor for the applicable function.
The primary function of the Dual Float Brine Sensor is to sense liquid in the brine-filled reservoir of the
interstitial area of a doubled-walled tank. Two (2) float switches are used in the body of the sensor to sense
fluid level changes. The device will cause an alarm condition in the system if the fluid level increases or
decreases more than the normal constant level in the middle between the upper and lower floats. If there is a
break in the cable it will cause an alarm condition in the system.
Since this sensor is not made to sense hydrocarbons it does not use a carbon/polymer strip.
No Carbon/Polymer Strip