Dover ProGauge MagLink LX Plus - 11.2 DMP Probe Installation Steps

Dover ProGauge MagLink LX Plus
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
n Measurement resolution: +/- 0,01 mm. (+/- 0.0001 mm for EPA option)
n Measurement repeatability: +/- 0,05 mm.
n Temperature accuracy: +/- 0,2°C (up to 5 temperature sensor option is available for static leak
test)
n Temperature resolution: 0.0625°((0.0001 °C for EPA option)
Approvals
l ATEX
l PESO
l UL
l UL_BR
l IECEx
l OIML-R85
l EPA
11.2 DMP Probe Installation
The Dover Magnetostrictive Probe (DMP) is installed almost the same as a 924B Probe.
IMPORTANT: To prevent damage to the probe, be careful when you remove the probe from
its packaging and when you install it in a tank. Do not let probe components hit the sides of
manholes or tank openings. Make sure the stainless steel probe shaft does not get bent. This
can cause incorrect indications in fluid levels.
IMPORTANT: If the fitting is not in the center of the tank, a Product Offset Calculation will be
necessary. See Product Offset Calculation for information.
DMP Probe with OPW-FMS Floats
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 41