NOTICE: The Density Measurement Float is not to be used in a pressurized tank.
13.2 Tank Thresholds
l When the Density Float is installed, the Product Float cannot be installed between the Water Float and
the Density Float. The product Float must be installed above the Density Float.
l The Low Product Alarm must be set above the Density Float.
l To set the Low-Low Product Alarm, measure the distance X and add 50mm (where the distance X is
from the bottom of the probe to the top of the Density Measurement Float).
13.3 Calibration on First Installation
To have a correct density reading the Density Measurement Float has to be put fully in the fuel.
During the first installation it is recommended to do a calibration with a third-party density meter
(hydrometer); the B parameter will change according to the alignment.
The calibration process will be shown in the configuration section of your console.
The density kit can lose its calibration because of the weight of possible contamination.
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 57