14.9 Interstitial Hydrocarbon Liquid Sensor with Water Indicator
Smart Sensor Equipped with Intellisense™ Technology
30-0234-HW-01
Description
The primary function of the Interstitial Hydrocarbon Liquid with Water Indicator Sensor is to sense liquid
hydrocarbons and water in the interstitial area of a double-walled tank. The sensor has a carbon/polymer
material that changes its resistance when it is touched by liquid hydrocarbons. The sensor also has a
conductive strip to sense water. This lets the sensor tell the difference between hydrocarbon liquid and
water. If there is a break in the cable it will cause an alarm condition in the system.
Specifications
Operating Temperature: -40°C to +70°C (-40°F to 158°F)
Dimensions: Length: 35 cm (13.8 in.), Width: 2.5 cm (1.0 in.)
Nominal resistance (uncontaminated) Less than 3,000 ohms per foot
Nominal resistance (contaminated) More than 10,000 ohms
Cable: Belden #88760 or Alpha #55371
Maximum Wiring Length*: 1,000’ (305 m) field wiring
Multi-Drop Restriction
Maximum points per channel = 12 points,
924B and DMP Probes = 4 points,
ISIM Smart Sensors = 1 point
Devices can be mixed in any combination to hold a maximum of 12
points on one channel
Connections: Red = Power, Black = Signal, Shield: = Ground
NOTE: *This is the maximum length of wire to be used to connect all sensors on one channel.
This length includes the wire from the Barrier to each sensor board in the string.
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 88