IMPORTANT: Wait a minimum of two (2) minutes before you supply power to the console
again after it has been put in the Off position. This will give the console time to fully shut down.
Element Description
USB
For USB printer connection. It can also be used for firmware updates and back-up of
the console (Refer to the M2052 MagLink LX 4/LX Plus User Manual)
RJ45
For console configuration, and local network connections (Refer to the M2051
MagLink LX 4/LX Plus Configuration Manual )
RS232 Com 1 Serial port for connection to management systems (FCC/POS/DCD)
RS232 Com 2 Serial port for connection to management systems (FCC/POS/DCD)
Ground
connection
Ground connection of the internal Intrinsically Safe barrier. Use a dedicated
4.0 mm
2
copper cable to connect to the main ground lug in the electrical panel of the
station. This will prevent high voltages sent to the Intrinsically Safe wiring side if
there is an electrical fault in the power side.
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 12