Product Density and Chemical Compatibility
Product Group
Compatibility
API Specific Gravity
Gasoline
Gasoline
Aviation Gasoline
Regular Unleaded
Regular Leaded
Premium Unleaded
Gasoline/Methanol blend, less than 5% methanol
Gasohol, less than 40% ethanol
45 < API < 78 0.68 < d < 0.80
Diesel
Diesel
Jet Fuel
Kerosene
Motor Oil
Toluene
Gear Oil
Transmission Oil
26 < API < 45 0.80 < d < 0.90
WARNING: THIS IS A STATIC SENSITIVE DEVICE! To prevent the risk of
explosion from static discharge, do not clean or rub this device with a dry
cloth.
NOTICE: To prevent damage to the I.S. barrier, you must turn off the power to the module
that the probe is connected to before you begin the procedure below.
1. Turn off the power to the module that the probe is connected to before you remove the probe from the
tank.
2. Remove the probe from the tank and remove the clip and the nylon probe foot from the bottom of the
probe.
3. Remove the water float. Put the density float on the probe shaft (make sure the top of the float points
toward the probe head) and tighten the screws of the float (the screws are at the top of the float). Keep
a space of 10.2 cm to 15.2 cm (4 to 6 inches) at the bottom of the probe shaft so the water float can
detect at least 7.6 cm (3 inches) of water.
4. Put the water float, nylon probe foot and end clip back on the probe shaft.
5. Put the probe back in the tank.
6. Turn on the power to the module.
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 53