Specifications
Detects: Liquid
Operating Temperature: –20°C to +50°C (–4°F to +122°F)
Dimensions - 30-0231-S Diameter: 1.3 inches (3.4cm), Length: 3.9 inches (10 cm)
Cable Requirements:
Belden #88760 or Alpha #55371
4.5m (15 feet) of gas & oil resistant cable to the inline ISIM
+ 1.3m (4 feet) ISIM tail.
Maximum Wiring Length*: 1,000’ (305 m) field wiring
Alarm Threshold Configuration: Fully Automatic
Diagnostic Reading on sensor setup:
0 - 0.5 (normal),
485 - 495 (in alarm)
Multi-Drop Restriction
Maximum points per channel = 12 points,
924B and DMP Probes = 4 points, ISIM Smart Sensors = 1 point
Devices can be mixed in any combination to hold a maximum of 12
points on one channel
Connections: Red = Power, Black = Signal, Shield = Ground
NOTE: *This is the maximum length of wire to be used to connect all sensors on one channel.
This length includes the wire from the Barrier to each sensor board in the string.
Installation
WARNING: Make sure you read and fully understand the warnings and
information found in the Hazardous Areas section of your console's
Installation Guide before you install or do the servicing of this sensor.
IMPORTANT: This Smart Sensor must ONLY be connected to an OPW Fuel Management
Systems 12V VSmart Module. This will make sure that operation conditions are safe. Smart
Sensors CANNOT be used with SS1, 2 or 3, iTouch or EECO consoles.
CAUTION: ALWAYS obey Local and National Electrical Codes applicable to
the installation location.
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 62