Typical Installation Drawing
Controller Setup
The sensor must be Auto Detected on the console. Refer to the M2051 MagLink LX4/LX Plus Cofiguration
Manual, Admin Account > System Settings > Site Info for information for information about auto-detection.
Alarm thresholds are configured automatically through the Intellisense mechanism between the sensor and
the console.
Float Sensor Test
CAUTION: Use caution to prevent dangerous conditions when you do work in
a hazardous area.
Make sure that the area has sufficient airflow when you do a test or remove
contamination from the sensor. Make sure there are no open flames or hot
surfaces near the work area.
Sensor installed in a normally dry well
l Put the float in the HIGH position. This will cause an alarm condition in the controller.
l Put the float back in the LOW position. Make sure that the controller is not in an alarm condition.
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 74