Cutaway View of Sensor that Shows Internal Floats
Specifications
Primary Use(s):
DH-10: Fuel Dispenser Pan/Sump
DH-20: STP Sumps
Alternate Uses:
DH-10: STP Sumps
DH-20: Fuel Dispenser Pan/Sump
Detects: Low Liquid, High Liquid, Fuel
Operating Temperature: -40°C to +70°C (-40°F to 158°F)
DH-10 Dimensions:
DH-20 Dimensions:
Diameter: 5.8 cm (2.3 in.), Length: 28.2 cm (11.1 in.)
Diameter: 5.8 cm (2.3 in.), Length: 53.6 cm (21.1 in.)
Float Requirements: Low: 3.8 cm (1.5 in.), High: 27.9 cm (11 in.)
Nominal resistance (uncontaminated) Less than 5,000 ohms
Nominal resistance (contaminated) More than 30,000 ohms
Cable:
Belden #88760 or Alpha #55371
3.6 m (12 feet) of gas & oil resistant cable to the inline ISIM
+ 1.3 m (4 feet) ISIM tail