Controller Setup
The sensor must be Auto Detected on the console. Refer to the M2051 MagLink LX4/LX Plus Cofiguration
Manual, Admin Account > System Settings > Site Info for information for information about auto-detection.
Alarm thresholds are configured automatically through the Intellisense mechanism between the sensor and
the console.
Float Sensor Test
CAUTION: Use caution to prevent dangerous conditions when you do work in
a hazardous area.
Make sure that the area has sufficient airflow when you do a test or remove
contamination from the sensor. Make sure there are no open flames or hot
surfaces near the work area.
Sensor installed in a normally dry well
l Put the float in the HIGH position. This will cause an alarm condition in the controller.
l Put the float back in the LOW position. Make sure that the controller is not in an alarm condition.
Sensor installed in a normally wet well
l Put the float in the LOW position. This will cause an alarm condition in the controller.
l Put the float back in the HIGH position. Make sure that the controller is not in an alarm condition.
If the controller does not sense the alarm conditions simulated by these tests, look to see if the thresholds
and alarms are correctly programmed in the system. Look to see if the float is in the correct position (refer to
the applicable instruction above). A sensor or wiring fault will cause a system alarm. Do a continuity test in
the wiring and junction boxes. Make sure there is continuity with no short circuits.
Hydrocarbon Sensor - Functional Test and Remove Contamination
IMPORTANT: It is recommended to only do the procedures below when it becomes
necessary and only as a last alternative. These procedures can cause a decrease in the
original electrical resistance of the polymer. If possible, speak with a certified OPW-FMS
technician before you do these procedures.
NOTICE: Do not use fuel (gasoline, diesel etc.) to test or clean the sensor! Once the
carbon/polymer material has touched liquid hydrocarbon, it is possible that the sensor will
not return to its initial electrical resistance. This can have an unwanted effect on its
M2050-PLUS MagLink LX Plus Installation Manual | Dover Fueling Solutions 80