Electrical connection
21
WARNING
Loss of explosion protection!
Death or serious injury.
à Unless ordered otherwise, the actuator is supplied with non-Ex certified screw
plugs. Replace them prior to commissioning by appropriate cable glands to main-
tain explosion protection.
For explosion-proof actuators, additionally heed the points below:
According to IEC/EN60079-14, actuators and the pertaining switching and distri-
bution devices have to be considered within the framework of the protective ac-
tions for the connected mains.
When using a PTC thermistor in the motor, provide the pertaining certified tripping
device within the system.
When using a thermal protector in the motor, provide the pertaining certified over-
current relay within the plant.
When deploying the actuator in potentially explosive atmospheres, use cable
glands and screw plugs with certification for the respective application.
Electrical connection of explosion-proof actuators is exclusively made via appropri-
ately certified connection terminals in compliance with the terminal plan supplied.
To ensure required equipotential bonding, connect actuators via the outer earth
terminal to the equipotential compensation system, provided that no fixed and se-
cured metallic contacts with construction parts are available which are in turn con-
nected to the equipotential compensation system.
DREHMO actuators are not equipped with an internal protective device against fail-
ures within the power circuit.
5.2
Connection terminals
Various options are available for actuator connections. Refer to Technical data [}35]
for precise indications relating to possible cable cross sections and, if applicable, per-
taining tightening torques.