27
DEHUMIDIFIER INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
90-1857
CONDENSATE PAN, CONDENSATE PUMP AND FLOAT SWITCH
A condensate pan is recommended when suspending the dehumidifier over
finished areas or product. Adhere to local codes regarding draining of the
condensate pan. If a condensate pump is needed, install it in the condensate
pan (user provided) as well.
Install a condensate overflow safety switch (i.e. float switch) in the condensate
pan (user provided), remove the factory installed jumper wire between
the Float Switch terminals on the control and wire the float switch to the
dehumidifier as shown in Figure 27-1. Overflow safety switches on
condensate pumps can be wired to the Float Switch terminals in a similar
fashion.
FIGURE 27-1: FLOAT SWITCH WIRING TO USER INTERFACE
Drain installation
INSTALLATION
Normally closed
float switch
DHDH
Float
Switch