DEHUMIDIFIER INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Troubleshooting
Table 50-1:
Diagnostic Codes (continued)
Diagnostic
Code Failure Mode Action Reset
E5 High Temperature
Thermistor Failure
Check the high temperature sensor connection at the power board. Terminal should be
fully seated on the power board pins.
Remove the side access panel and verify the sensor is not damaged and connected to the
refrigeration line coming from the compressor.
If the sensor is connected and secured to the refrigeration line, it may need to be
replaced. Contact Technical Support to confirm.
Cycle Power
E6 Low Temperature
Thermistor Failure
Check the low temperature sensor connection at the power board.
Remove the side access panel and verify the sensor is not damaged and connected to the
suction line.
Terminal should be fully seated on the power board pins.
If the sensor is connected and secured to the refrigeration line, it may need to be
replaced. Contact Technical Support to confirm.
Self-
Correcting
E7 Float Switch Open Empty the condensate pan.
Check the float switch connection at the control board.
If not using a float switch, verify jumper is between float switch terminals on dehumidifier
control board.
If the problem persists, replace the float switch.
Self-
Correcting
E8 Inlet Air
Temperature Out
of 50°F – 104°F
(10°C - 40°C)
Range or Dew
Point Below 36°F
(2.2°C) for RL-31
and below 40°F
(4.4°C) for all
other models.
Verify all ductwork is properly sealed.
If no signs of leak points, contact Technical Support.
Self-
Correcting
E9 Fan or Compressor
Fault
Cycle power. If problem persists, contact Technical Support. Cycle Power