DEHUMIDIFIER INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
TROUBLESHOOTING
Table 51-1:
Troubleshooting
Symptom Possible Reason Troubleshooting Procedure
Dehumidifier does not
turn on/run.
No power to unit. Check that the dehumidifier is plugged in.
Check that the power switch is turned ON.
Check that the control is turned ON.
Check that the circuit breaker has not tripped.
Check demand for dehumidification.
Measured humidity must be greater than control setpoint.
Dehumidifier blower
is running but with
little or no airflow.
Pressure drop across
dehumidifier is too
high.
Check dehumidifier air filter and replace if necessary.
Check for blocked duct work and clear.
Dehumidifier blower
is running but
compressor is not.
Float switch open. If float switch installed, check connections at control board and empty condensate pan.
If no float switch installed check that the jumper is installed at the float switch terminals on
the control board.
Coil frosting – defrost. Lack of or reduced airflow. Check dehumidifier air filter and replace if necessary.
Check for blocked duct work.
Inlet air conditions below 60°F (15.6°C). Increase the humidity setting.
Inlet air temperature
is outside of the
50°F – 104°F (10°C
- 40°C) range or the
dew point is below
36°F (2.2°C) and
there is a demand for
dehumidification.
Verify all ductwork is properly sealed.
Dehumidifier is not
draining properly.
Drain line blocked or
unit not level.
Verify that the unit is level.
Check the drain line blockages and for a continuous downward slope.
Dehumidifier is
producing hot air.
Normal function. Air is reheated across the condenser coil, resulting in a temperature rise between inlet and
outlet, this is normal.