Section 5: Programming
Note: Delinquency code is not transmitted while Away armed. Activity on bypassed zones does not affect this timer.
OFF: The Delinquency reporting code is sent when the programmed number of days for delinquency (section [377]) expires
without the partition being Armed. Once the code is sent, the timer is not started again until the partition has been armed.
Each day programmed in the counter represents one day plus the time it takes for the partition to reach midnight. To disable
this feature, program 000 in section [377]>[002] option 5.
[381] Communicator Option 2
1 Keypad Ringback
ON: When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number, the
keypad emits a series of 8 beeps to confirm to the occupant that the code was sent and received. Ringback occurs for each
successfully reported Opening After Alarm code.
OFF: When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number, the
keypad does not sound ringback.
2 Bell Ringback
ON: When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number, the siren
emits a series of 8 squawks to confirm to the occupant that the code was sent and received. Ringback occurs for each suc-
cessfully reported Opening After Alarm code.
OFF: When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone number, the siren
does not sound ringback.
4 Closing Confirmation Enabled/Disabled
ON: When a Closing reporting code is successfully transmitted to a programmed telephone number, the keypad emits a
series of 8 beeps to confirm to the occupant that the Closing Code was sent and received.
OFF: No keypad ringback is generated when a Closing reporting code is successfully transmitted.
8 Communications Priority Enabled/Disabled
ON: Events follow the priority level indicated in ULC-S559 standard.
Concurrent event communications are prioritized in the following order (highest to lowest priority):
1. Fire Alarms
2. CO Alarm
3. Fire Supervisories
4. Fire Trouble
5. Monitoring (Medical, Panic or Security)
6. All others such as restorals for fire alarms, supervisories, troubles and monitoring.
7. FTC'ed events
OFF: Events are communicated in the order they occur.
ULC
Note: Must be ON for ULC commercial fire monitoring listed installations.
[382] Communicator Option 3
1 Not Used
2 Walk Test Communications
ON: Zone alarms that occur during Walk Test are communicated if programmed to do so.
OFF: Zone alarms during Walk Test are not communicated. FMP key alarms are still communicated.
4 Call Waiting Cancel
ON: The call waiting cancel string (See "[304] Call Waiting Cancel String" on page 100) is used on the first attempt to dial
each phone number. It is not used on any further dialing attempts.
OFF: The call waiting cancel string is not dialed.
5 Alternate Communicator Enable/Disable
ON: The system communicates using the alternate communicator. All related programming options, reporting and super-
vision are enabled when programmed via PC-Link2.
- 111 -

Table of Contents

Other manuals for DSC HS2016

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DSC HS2016 and is the answer not in the manual?

DSC HS2016 Specifications

General IconGeneral
Mounting TypeWall mount
Power Supply16.5VAC
Battery Backup12VDC
Operating Temperature32°F to 120°F (0°C to 49°C)
Dimensions267mm

Related product manuals