Section 4: System Operation
seconds during this warning period if programmed to do so. When the warning period is complete, the exit delay elapses
then the system arms in away mode.
Auto-arming can be canceled or postponed only by entering a valid access code during the programmed warning period.
When a code is entered, the warning is silenced and auto-arming is canceled or postponed, depending on the auto-arm
postpone timer. The Auto Arm Cancellation reporting code is transmitted (if programmed).
Note: Auto-arming will not silence an active bell.
Note: The Auto Arm Cancellation reporting code is also transmitted if arming is inhibited by one of the following:
l AC / DC Inhibit Arm
l Latching System Tampers
l Zone Expander Supervisory Fault
Other programming options that may affect this function:
See "[151]-[158] Partition Auto-Arm/Disarm" on page 98
See "[014] System Option 2" on page 87
Enable DLS/Allow System Service
Menu: [*][6][Master Code] > System Serv/DLS
Keypad: [*][6][Master Code] + 05
This function enables and disables the DLS window for either 1 or 6 hours depending on the programming of section [025]
option [7].
This function also enables the end user to provide or deny access to [*][8] Installer Programming. When enabled, the
installer can access Installer Programming either by DLS or via [*8] if a pre-programmed window has been set. After the win-
dow has expired, Installer Programming is unavailable again until the window is re-opened.
Note: DLS programming is not UL tested.
Other programming options that may affect this function:
See "[020] System Option 8" on page 92, and see "[021] System Option 9" on page 93
See "[025] System Option 13" on page 96, bit "7 – 1 Hour DLS Window"
User Call-up
Menu: [*][6][Master Code] > User Call-up
Keypad: [*][6][Master Code] + 06
When selected, this function makes a single attempt to call the downloading computer. The downloading computer must be
waiting for the call before downloading can be performed. Only one call-up is attempted. If a DLS phone number is not pro-
grammed, the alarm panel attempts to reach the DLS computer via IP connection. If the communicator is not properly con-
figured for IP, an error tone is sounded.
User Walk Test
Menu: [*][6][access code] > Walk Test
Keypad: [*][6][access code] + 08
Selecting this function places the alarm panel into user walk test mode. The Ready, Armed and Trouble LEDs on the keypad
flash to indicate that the test is active. If zones are tripped during a walk test, the system sounds a steady 2-second tone on
all keypads to indicate that the zone is working correctly.
The walk test can be stopped at any time by re-entering [*][6][Master Code][08] on the keypad. The test automatically ter-
minates after 15 minutes of inactivity. An audible warning begins 5 minutes prior to automatic termination.
Note: Fire and CO alarms are not tested in user's walk test. If a fire or CO alarm is detected, walk test ends automatically and the
appropriate reporting codes are sent immediately to the monitoring station. Refer to the manufacturers instructions provided with
CO and Fire detectors for testing. This feature is not available in CP-01 systems.
Late to Open
Menu: [*][6][Master Code] > Late To Open
Keypad: [*][6][Master Code] + 09
This function enables or disables the Late to Open option. This option sends a reporting code to the central monitoring sta-
tion if the partition has not been disarmed by a programmed time.
Other programming options that may affect this function:
- 51 -