49
* A/R = alarms/restorals; O/C = openings/closings; O = other
** PPP = partition number; UUU = user number (user 1000 to 1500 = 999); ZZZ = zone number
Ref. # Reporting Code Code Sent When...
Dialer
Direction*
Contact
ID
SIA Auto Rep
Codes**
[00040309] Waterflow Trouble/Rest. waterflow zone has trouble (open) condition
(PC4701 only)
A/R (3) 73 ST-998/SJ-998
[00040309] Fire Test Begin fire inspector's test start & fire drill test begins A/R (6) A4 FI-000
[00040309] Fire Test End fire inspector's test end & fire drill test ends A/R (6) A4 FK-000
[00040309] Fire Bypass/Unbypass fire zone bypassed/unbypassed A/R (5) 71 FB-ZZZ/FU-ZZZ
[00040310] User Closings partition armed (user 001-128 indicated) O/C (4) A2 CL-UUU
[00040311] Closing 129-1500 user code # 129-1500 used to arm partition O/C (4) A2 CL-UUU
[00040311] Special Closing O/C (4) A2 CL-000
[00040311] Partial Closing one or more zones intentionally bypassed
when partition armed
O/C (4/5) 56 CW-000
[00040311] Automatic (Scheduled) Clos-
ing
auto arming according to schedule O/C (4) A3 CA-000
[00040311] Auto Arm Cancellation auto arm cancelled O/C (4) A5 CE-000
[00040312] Partition Closing partition armed (partition number indicated) O/C (4) AA CG-PPP
[00040313] User Openings partition disarmed (user 001-128 indicated) O/C (4) A2 OP-UUU
[00040314] Opening 129-1500 user code # 129-1500 used to disarm partition O/C (4) A2 OP-UUU
[00040314] Special Opening disarm with WLS909, Second Master code,
keyswitch, downloading or guard code
O/C (4) A2 OP-000
[00040314] Automatic (Scheduled)
Opening
auto disarming according to schedule O/C (4) A3 OA-000
[00040314] Door Shunt PC4820 zone shunted while armed O/C (5) 76 DG-222
[00040315] Partition Opening partition disarmed (partition number indi-
cated)
O/C (4) AA OG-PPP
[00040316] Battery Trouble/Rest. PC4020 battery is low O (3) A2 YT-000/YR-000
[00040316] AC Line Trouble/Rest. AC power to control panel is disconnected or
interrupted
O (3) A1 AT-000/AR-000
[00040316] Panel Bell Trouble/Rest. open circuit detected across bell terminals O (3) 21 YA-000/YH-000
[00040316] Panel Auxiliary Trouble/Rest. aux voltage supply trouble O (3) AA YP-000/YQ-000
[00040316] Combus Trouble/Rest. control panel loses communications with con-
nected module(s) or has low power
O (3) 33 UT-000/UJ-000
[00040316] TLM Failure/Rest. telephone line 1 monitoring trouble (sent via
LINKS. Do not program if LINKS not used)
O (3) 51 LT-001/LR-001
[00040316] TLM Line2 Failure/Rest. telephone line 2 monitoring trouble (sent via
LINKS. Do not program if LINKS not used)
O (3) 52 LT-002/LR-002
[00040316] FTC Restoral control panel has restored communications to
central station (after TLM Fail)
O (3) 54 YK-000
[00040316] Buffer Near Full printer not used or off-line for 450 events O (3) None JL-000
[00040316] User System Test [*][6] bell/communications test O (6) A1 RX-000
[00040316] Periodic Test periodic test transmission O (6) A2 RP-000
[00040316] Periodic Test Tbl periodic test transmission trouble O (6) A7 RP-001
[00040316] LINKS Test LINKS test transmission O (6) A3 TX-000
[00040316] Ground Fault/Rest. EGND connection detects a ground fault O (3) 1A US-000/UR-000
[00040316] DLS Lead In DLS Call Back feature only: downloading ses-
sion start
O (4) 11 RB-000
[00040316] DLS Lead Out DLS Call Back feature only:
downloading session complete
O (4) 12 RS-000
[00040316] Installer Lead In Installer code has been entered O (4) 58 LB-000
[00040316] Installer Lead Out Installer's programming complete O (4) 58 LS-000