PowerSeries Neo Installation Guide
Each of the above examples is under the sole responsibility of a single owner.
The bell and DACT power supply must be in a protected area including
partitioned systems. The bell and DACT power supply must be located where it
can be heard by the person or persons responsible for maintaining the security
system during the daily arming cycle.
Bell Location
The alarm sounding device (bell) shall be located where it can be heard by the
person operating the security system during the daily arming and disarming cycle.
Protection of the Control Unit
The local control unit and the local power supply must be protected in one of the
following ways:
l The control unit and audible alarm device must be in a protected area which
is armed 24 hours a day.
l Each partition must arm the area protecting the control unit and the audible
alarm device power supply. This may require duplicate protection armed by
each partition. Access to this protected area, without causing an alarm, will
require that all partitions be disarmed.
l In all cases described above, the protected area for the control unit must be
programmed as not-bypassable.
Casual Users
The installer should caution the user not to give system information (e.g., codes,
bypass methods, etc.) to casual users (e.g., service people) and to only give out
One-Time Use codes.
User Information
The installer should advise the user and note in the Users Manual:
l Service organization name and telephone number
l The programmed exit and entry time
l Instructions to test system weekly
l Note that the installer code cannot arm or disarm the system
- 20 -