136
Analogtrigger:Ax
Analogamplifier:Ax
Analogmultiplexer:AQ
Analogramp:AQ
Analogmath:AQ
PIcontroller:AQ
Datalatchingrelay:AQ
Up/Downcounter:Cnt
Thevalueof "MI" canbesetandmodifiedinparametermode.Forinformationabouthowtomodify,
refertochapter4.2.2please.
Descriptionofthefunction
ThehourscountermonitorsinputEn.Aslongasthestatusatthisinputis1,xLogiccalculatesthetime
expiredandthetime-to-goMN.xLogicdisplaysthesetimeswhensettoconfigurationmode.Theoutput
issetto1whenthetime-to-goisequaltozero.
YouresetoutputQandthetime-to-gocountertothespecifiedvalueMIwithasignalatinputR.The
operationhourcounterOTremainsunaffected.
YouresetoutputQandthetime-to-gocountertothespecifiedvalueMIwithasignalatinputRal.The
operationhourcounterOTisresetto0.
DependingonyourconfigurationoftheQparameter,theoutputiseitherresetwitharesetsignalatinput
RorRal,orwhentheresetsignalis1ortheEnsignalis0.
LimitvalueofOT
ThevaluesoftheoperatinghoursinOTareretainedwhenyouresetthehourscounterwithasignalat
inputR.ThehourscounterOTcontinuesthecountaslongasEn=1,irrespectiveofthestatusatthe
resetinputR.ThecounterlimitofOTis99999h.Thehourscounterstopswhenitreachesthisvalue.
Inprogrammingmode,youcansettheinitialvalueofOT.Thecounterstartsoperationatanyvalueother
thanzero.MNisautomaticallycalculatedattheSTART,basedontheMIandOTvalues.
Example:MI=100,OT=130,theresultisMN=70
Parameterpreset
InxLogicsoft,youcandefineMIandanOTstartvalue.
YoudeterminethatQdoesnotdependonEnbyselectingthecorrespondingcheckbox.
Retentivitywiththehourscounter
ThehourscounterinthexLogicisgenerallyretentive.
However,ifthevaluesofthehourscounterarelostafterapowerfailure,thenselecttherespectiveblock
inyourcircuitprogram.RightmouseclickonthehourscounterandselectBlockProperties>Parameters.
TheoptionRetentivitymustbeactivatedandnotchangeable(grayedout).
Ifthe Retentivity optionisnotavailable,thendeletetheblockandinsertanewspecialfunction hours
counter atthesameposition.