28 FX6000 INSTALLATION AND OPERATION MANUAL 25-14683-C December 2019 www.eaton.com
Compatible Equipment
Micro interfaces
A range of micro interfaces modules are also available:
MIU872 is a compact single zone input, soft addressed, microinterface, incorporating
integral short circuit isolators. It is fully compatible with the current range of Eaton
analogue fire detection panels. It is suitable for interfacing a zone of up to 20
conventional Eaton detectors onto a Eaton analogue fire panel. It will operate with
any Eaton conventional detector in configuration with a schottky diode type base.
400008FIRE-0022X (MCIM) is a compact input module used to accept input signals
from external equipment such as beam detectors, flow switches, valve monitor
switches etc. The panel can be programmed to perform different actions based on
the state of the input. The maximum number of input devices per loop is 200.
400010FIRE-0024X (MCOM) is a compact single channel output unit for general
external equipment control. This device is identified as an I/O device by a Eaton
addressable panel. The maximum number of I/O devices per loop is 20.
400012FIRE-0026X (MCOM-S) is a compact single channel output unit. This device
is identified as a sounder output by a Eaton addressable panel and will react to
evacuate commands. The maximum number of sounder devices per loop is 60.
400011FIRE-0025X (MCOM-R) is a compact single channel output unit used to
control or signal external equipment which require removal of power for reset
purposes. This device is identified as an I/O device by a Eaton addressable panel.
The maximum number of I/O devices per loop is 20.
MCOM-FC is a compact single channel output unit used in conjunction with the
Fan Controller (FC6/FC18) for the control of smoke extraction fans. This device is
identified as a sounder output by a Eaton addressable panel but does not react to
the evacuate command. The maximum number of sounder devices per loop is 60.

Table of Contents