90 FX6000 INSTALLATION AND OPERATION MANUAL 25-14683-C December 2019 www.eaton.com
Panel controls & indicators
Analogue level
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission, then Press Analogue Levels”.
Service
FRE Off
Commission
Test
Congure
001 Device 1, Zone 1
Loop: 1, Zone: 1, Type: Opto/thermal
002 Device 2, Zone 1
Loop: 1, Zone: 1, Type: Opto/thermal
003 Device 3, Zone 1
Loop: 1, Zone: 1, Type: Opto/thermal
004 Device 4, Zone 1
Loop: 1, Zone: 1, Type: Opto/thermal
005 Device 5, Zone 1
Loop: 1, Zone: 1, Type: Opto/thermal
Exit
Exit
Goto
Reset
Reset
Service
FRE off
Show
D
etectors
Show
O
ptical
Show
I
onisation
Show
Thermal
Show
A
ll
Enter Address
Cancel
Loop 1
0 - 13
Loop 2
0 - 0
Loop 3
0 - 0
Loop 4
0 - 0
1
4
5
6
7
8
9
ok
0
2
3
..................
Mute
Buzzer
Note: go to command can be used
to jump to a specic address
Exit
Reset
Service
FRE Off
Load logo from PC
Analogue Level
Auto Learn
Printer Settings
Change Panel Number
Number of Panels
in Network
Commission devices to
hybrids (26V mode)
Download CDR to Laptop
Erase Log
Load CDR from Laptop
Mute
Buzzer
Screen Cover
System Details
Evacuate
Silence
Alarms
Mute
Buzzer
Reset
Supervisor
FRE off
Others
Print
View Fires
AC = 1378
V
iew Pre
Alarms
View
Disabled
View
Faults
Weekly Test
Enable/Disable
View Log
Send Log to PC
Check Config.
Send analogue values to PCLamp Test
Exit
Address 5
Ground floor
Address 5
Panel 2
Loop 1
Optical
Enabled
Alarm >= 60
PreAlarm 49
Fault <= 5
Current 21
Min 21
Max 21
Previous Next Reset
Service
F
RE off