49FX6000 INSTALLATION AND OPERATION MANUAL 25-14683-C December 2019 www.eaton.com
Installation
Fixing details
Read all the installation instructions before commencing with the installation.
The installation of this panel must be carried out by a suitably qualified /trained
person. The installation must comply with IEE wiring regulations and with
BS5839 part 1 2002.
The electronic components within the fire panel are Static Sensitive.
Do not touch the electronics directly.
Mounting the backbox
The panel can be flush mount or surface mounted.
1. Surface Mount; drill four holes and fix the backbox to the wall
1. Flush mounting the backbox requires a hole 364x 472 with a depth of
117mm (standard battery / backbox ) or 217 mm if deep backbox is used
Installing Cabling
Once the backbox is mounted the next stage is to install the power and loop cables
and fit the glands.
364mm
117mm
132mm
472mm
227mm
309mm
400mm
479mm