45FX6000 INSTALLATION AND OPERATION MANUAL 25-14683-C December 2019 www.eaton.com
Technical specification
Alarm verification (Option not required by EN54 pt2)
This mode is programmed at access level 3. This has the flexibility to delay the
activation of detectors by 30 seconds.
In the event of an alarm from a detector, the led of the detector will be illuminated
and no alarm will be displayed on the panel. The detectors are checked continuously
for 30 seconds. If after this time, the detector is still in alarm, the output will be
activated otherwise the detector will be reset.
Timer T1/T2 (Option not required by EN54 pt2)
This mode is set on at access level 3 and is a commonly used by
Eastern European Countries.
In the event of a Fire the timer T1 can be set from 1 to 3 mins where the alarm will
be displayed on the panel and no output activation, if during this time the alarm is
acknowledged then timer T2 can be set from 1-10 mins where the alarm can be
investigated and alarm reset.
However if timer T1 & T2 time out during alarm activation, the outputs
will be activated.
Timer T1/T2 with Call point Override (Option not required by EN54 pt2)
This is similar to the above except a call point alarm will activate the output instantly.