Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15 17
The system must be installed in a temperature and humidity controlled indoor area free of conductive
contaminants.
Failure to follow guidelines may void your warranty.
The UPS equipment operating environment must meet the weight requirements shown in Table 2 and the size
requirements shown in Figure 5 through Figure 18. Dimensions are in millimeters (inches).
Table 2 does not include the weight of the Field Installed UPM (FI-UPM). For Field Installed UPM (FI-UPM)
weights and dimensions, refer to the Eaton 9395 Field Installed UPM Mechanical Installation Manual, listed in
paragraph 1.7 For More Information.
Table 2 Includes the weights of the heaviest cabinet configuration. Actual weights may be less due to installed
configuration. Weights are in kilograms (pounds).
Table 2. UPS Cabinet Maximum Weights
Model
Section
Maximum Weight kg (lb)
Shipping
Installed
Power Xpert 9395-825/450
Power Xpert 9395-825/500
Power Xpert 9395-825/550
ISBM (CSS) 862 (1900) 829 (1828)
UPM (Two UPM) 1152 (2541) 1125 (24181)
Power Xpert 9395-825/650
Power Xpert 9395-825/750
Power Xpert 9395-825/825
ISBM (CSS) 862 (1900) 1485 (3274)
UPM (Three UPM) 1724 (3802) 1688 (3722)
NOTE: CSS = Continuous Static Switch
The UPS cabinets use forced air cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are in the top. Allow clearance in front of and above each cabinet for proper air
circulation. The clearances required around the UPS cabinet are shown in Table 3. Dimensions are in
millimeters (inches).
Table 3. UPS Cabinet Clearances
From Top of Cabinet 457.2 mm (18") minimum clearance for ventilation
From Front of Cabinet
914.4 mm (36") working space
From Back of Cabinet
None Required
From Right Side of Cabinet None Required
From Left Side of Cabinet
None Required
The basic environmental requirements for operation of the UPS are:
Ambient Temperature Range: 0–40º C (32–104º F)
Recommended Operating Range: 20–25º C (68–77º F)
Maximum Relative Humidity: 95%, non-condensing