18 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
If Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental
requirements supercede the UPS requirements. Operating temperatures above the recommended range will
result in decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton’s
Terms and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book for
more information. These documents can be found at www.eaton.com/ powerquality or contact an Eaton
service representative to obtain copies.
The UPS ventilation requirements are shown in Table 4.
Table 4. Air Conditioning or Ventilation Requirements During Full Load Operation
Model
Rating
Input/Output
Voltage
Heat Rejection BTU/hr
x1000 (kg-cal/hr)
Ventilation Required for
Cooling Air Exhaust
Power Xpert
9395-825/450
450 kVA
400/400 87 (21886)
Approximately 1652 liter/sec (3500
CFM)
With Field Installed UPM:
Approximately 2478 liter/sec (5250
CFM)
480/480 88 (22107)
Power Xpert
9395-825/500
500 kVA
400/400 96 (24318)
480/480 97 (24563)
Power Xpert
9395-825/550
550 kVA
400/400 106 (26479)
480/480 107 (27020)
Power Xpert
9395-825/650
650 kVA
400/400 125 (31613)
Approximately 2478 liter/sec (5250
CFM)
With Field Installed UPM:
Approximately 3304 liter/sec (7000
CFM)
480/480 127 (31933)
Power Xpert
9395-825/750
750 kVA
400/400 145 (36476)
480/480 146 (36845)
Power Xpert
9395-825/825
825 kVA
400/400 159 (40124)
480/480 161 (40530)
Power Xpert
9395-825/650
650 kVA
(IOM)
400/400 125 (31613)
Approximately 2478 liter/sec (5250
CFM)
With Field Installed UPM:
Approximately 3304 liter/sec (7000
CFM)
480/480 127 (31933)
Power Xpert
9395-825/700
750 kVA
(IOM)
400/400 145 (36476)
480/480 146 (36845)
Power Xpert
9395-825/825
825 kVA
(IOM)
400/400 159 (40124)
480/480 161 (40530)
NOTE CSS = Continuous Static Switch
UPS Installation Plan and Unpacking