INSTALLATION
EATON Powerware
®
9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com
28
NOTE A separate contact must simultaneously cause UPS input AC power to be removed.
Pin 1 Pin 2
Figure 13. REPO Connector
4. Connect the REPO connector to the REPO port on the UPS rear
panel.
5. Verify that the externally-connected REPO switch is not activated to
enable power to the UPS output receptacles.
6. Plug in the UPS and start the UPS by pressing the On
button.
7. Activate the external REPO switch to test the REPO function.
8. De-activate the external REPO switch and restart the UPS.