9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com
37
Chapter 5 Configuration
When the UPS is in Configuration mode, the bar graph indicators
represent the configuration options. Use the control buttons
(On
button and button) to modify the UPS configuration. Figure 21
shows the LEDs and Table 1 explains the corresponding options.
NOTE The UPS can be configured while in Battery mode. If the UPS transfers to battery
power while in Configuration mode, the UPS remains in Configuration mode and indicates
Battery mode on the front panel after exiting Configuration mode.
CAUTION
DO NOT press the Off button while the UPS is in Configuration mode; pressing the
Off button removes all power to your equipment immediately and the UPS enters
Standby mode.
To reconfigure the UPS default settings:
1. Press and hold the On
button and the button simultaneously
for approximately three seconds. The UPS transfers to
Configuration mode.
The LEDs flash briefly and then display the enabled options.
2. Press the On
button to scroll through the options. Each time you
press the button, the UPS beeps. The LED for the selected option
indicates the current setting; flashing represents disabled options
(see Figure 21 and Table 1).
Scrolling past the last LED returns to the first configuration option.
If you press the On
button and nothing happens, the UPS is still in
Operation mode. Repeat Step 1 to enter Configuration mode, and
then perform Step 2.
3. Press the
button ONCE to select the Voltage option or to toggle
the Site Wiring Fault Alarm or AC Input Failure Alarm on or off.
NOTE The UPS automatically exits Configuration mode after two minutes.