EATON Powerware
®
9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com
41
Chapter 6 Additional UPS Features
This section describes:
S X-Slot cards
S Network transient protector
S Load segments
X-Slot Cards
X-Slot cards allow the UPS to communicate in a variety of networking
environments and with different types of devices. The Powerware 9125
is factory-installed with a Single-Port Card or USB Card, depending on
the customer order.
S ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities
as well as monitoring through a Web browser interface; connects to a
twisted-pair Ethernet (10/100BaseT) network. It has a built-in
switching hub that allows three additional network devices to be
connected to the network without the requirement of additional
network drops. In addition, a Powerware Environmental Monitoring
Probe can be attached to obtain humidity, temperature, smoke alarm,
and security information.
S Relay Interface Card - has isolated dry contact (Form-C) relay outputs
for UPS status: Utility failure, Low battery, UPS alarm/OK, or On
bypass.
S Modbus
®
Card - allows you to continuously and r eliably monitor t he
UPSs in your Building Management System (BMS).
S Multi-Server Card - has six serial communication ports that can
communicate simultaneously with other computers using Powerware
LanSafe
®
Power Management Software (provided on the Software
Suite CD).
S Single-Port Card - connects to the Powerware Expansion Chassis to
enable multiple communication options or to a PC for power
management control.
S USB Card - connects to a USB port on your computer.
t