OPERATION
EATON Powerware
®
9125 Two-in-One UPS (700–2000 VA) User’s Guide S 164201514 Rev B www.powerware.com
32
Turning the UPS Off
NOTE Pressing the Off button while the UPS is in Battery mode causes the UPS to shut
down immediately.
To turn off the UPS:
1. Prepare your equipment for shutdown.
2. Press and hold the Off
button for approximately three seconds.
The UPS transfers to Standby mode (if utility power is available) and
removes power from your equipment.
3. Unplug the UPS; the UPS shuts down in five seconds. All front
panel indicators flash briefly twice prior to shutdown.
If you do not unplug the UPS, it remains in Standby mode.
Initiating the Self-Test
NOTE The batteries must be fully charged and the UPS must not be in Battery mode to
perform the self-test.
NOTE Load must be applied to the UPS to perform the battery test. Apply the following
load amounts according to the UPS rating: 50% load for 700 VA; 35% load for 1000 VA; 45%
load for 1250 VA; 38% load for 1500 VA; or 25% load for 2000 VA.
Press and hold the button for three seconds to initiate the self-test.
During the five-second test, the bar graph indicators cycle through twice.
If the alarm beeps or a UPS alarm indicator stays on, see Table 10 on
page 58.