Chapter 3—Product Overview
DG1 Series VFD MN040002EN—March 2014 www.eaton.com 15
Maintenance and Inspection
DG1 frequency inverters are maintenance free. However, 
external influences may affect the function and the lifespan 
of the DG1 frequency inverter. We therefore recommend 
that the devices are checked regularly and the following 
maintenance measures are carried out at the specified 
intervals.
If the DG1 frequency inverter is damaged by external 
influences, contact Eaton Technical Service.
Table 13. Maintenance Measures and Intervals 
Storage
If the frequency inverter is stored before use, suitable 
ambient conditions must be ensured at the site of storage:
●
Storage temperature: –40°F to 158°F (–40°C to 70°C)
●
Relative average air humidity: <95%, noncondensing 
(EN 50178)
●
To prevent damage to the DC link capacitors, storage 
times longer than 12 months are not recommended
Charging the Internal DC Link Capacitors
After extended storage times or extended downtimes during 
which no power is supplied (>12 months), the capacitors in 
the internal DC link must be recharged in a controlled manner 
in order to prevent damage. To do this, the DG1 variable 
frequency drive must be supplied with power, with a 
controlled DC power supply unit, via two mains DC bus 
connection terminals. Please consult the factory for detailed 
instructions.
Service and Warranty
In the unlikely event that you have a problem with your DG1 
frequency inverter, please contact your local sales office.
When you call, have the following information ready:
●
the exact frequency inverter part no. (see nameplate)
●
the date of purchase
●
a detailed description of the problem that has occurred 
with the frequency inverter
If some of the information printed on the nameplate is not 
legible, please state only the information that is clearly 
legible. This information can also be found on the cover of 
the control terminals.
Information concerning the guarantee can be found in the 
Eaton General Terms and Conditions of Sale.
Maintenance Measure Maintenance Interval 
Clean cooling vents (cooling slits)  If required 
Check the fan function 6–24 months (depending 
on the environment) 
Filter in the switching cabinet doors 
(see manufacturer specifications)
6–24 months (depending 
on the environment) 
Check the tightening torques of the terminals 
(control signal terminals, power terminals)
Regularly
Check connection terminals and all metallic 
surfaces for corrosion 
6–24 months (depending 
on the environment)