EasyManua.ls Logo

Eaton PowerXL DG1-323D7FB-C21C - Table 34. 230 V Temperature and Switching Frequency Deratings (CT)

Eaton PowerXL DG1-323D7FB-C21C
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix B—Installation Guidelines
DG1 Series VFD MN040002EN—March 2014 www.eaton.com 51
Table 34. 230V Temperature and Switching Frequency Deratings (CT)
Note
1
FR6 available in 2015.
Constant Torque
(CT) /High
Overload (I
H
)
Frame
Size
Percentage of Rated Current
Switching Frequency
Temperature 1 kHz 2 kHz 3 kHz 3.6 kHz 4 kHz 5 kHz 6 kHz 7 kHz 8 kHz 9 kHz 10 kHz 12 kHz
40°C FR1 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 95.9% 91.8%
FR2 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0%
FR3 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0%
FR4 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 96.2% 92.3% 88.5%
FR5 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 96.1% 92.2% 88.2%
FR6
1
1
1
1
1
1
1
1
1
1
1
50°C FR1 100.0% 100.0% 100.0% 100.0% 100.0% 97.7% 95.5% 91.8% 88.2% 84.5% 79.1% 73.6%
FR2 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 98.0% 96.0% 94.0% 91.0% 88.0%
FR3 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0% 100.0%
FR4 100.0% 100.0% 100.0% 100.0% 97.1% 94.3% 91.4% 88.5% 84.7% 80.8% 77.0%
FR5 100.0% 100.0% 100.0% 100.0% 95.1% 90.3% 85.4% 80.6% 74.5% 68.4% 62.4%
FR6
1
1
1
1
1
1
1
1
1
1
1
60°C FR1 83.6% 83.6% 83.6% 83.6% 83.6% 80.9% 78.2% 75.5% 72.7% 70.0% 65.9% 61.8%
FR2 92.0% 92.0% 92.0% 92.0% 92.0% 92.0% 92.0% 130.0% 168.0% 80.0% 101.3% 68.0%
FR3 91.7% 91.7% 91.7% 91.7% 91.7% 90.6% 89.6% 88.5% 87.5% 86.1% 84.7% 83.3%
FR4 83.9% 83.9% 83.9% 83.9% 80.7% 77.6% 74.4% 71.3% 67.4% 63.6% 59.8%
FR5 79.4% 79.4% 79.4% 79.4% 75.6% 71.8% 67.9% 64.1% 59.5% 54.9% 50.3%
FR6
1
1
1
1
1
1
1
1
1
1
1

Table of Contents